title: How do I configure a SMA Data Manager EDMM-20 for communication with the Maxem Energy Controller?
description: This article explains how to configure a SMA Data Manager EDMM-20 with the Maxem Energy Controller.
---

[Skip to content](https://support.maxem.io/how-do-i-configure-a-sma-edmm-20-data-manager-for-communication-with-the-maxem-energy-controller#main-content)

English

Show submenu for translations

[![Logo-white](https://support.maxem.io/hs-fs/hubfs/Logo-white.png?width=230&height=37&name=Logo-white.png)](https://maxem.energy/)

- Create support ticket
  
  Show submenu for Create support ticket

    - [Sales request](https://share-eu1.hsforms.com/2FZyysmEyRAKSZ2IKnHrf0Q2dyw99)
    - [Technical support](https://share-eu1.hsforms.com/26WB8z3cYTPWv02MIx6nr7w2dyw99)
    - [Finance support](https://share-eu1.hsforms.com/2mMsLOqRLQl2l8S6q3ZbgDA2dyw99)
    - [Report a bug](https://share-eu1.hsforms.com/220XTdV4ZQ726tz1CtoOw7A2dyw99)
    - [Feature request](https://share-eu1.hsforms.com/2g75JWLunRbqueEKBytvYvg2dyw99)

Open main navigation

Close main navigation

- Create support ticket
  
  Show submenu for Create support ticket

    - [Sales request](https://share-eu1.hsforms.com/2FZyysmEyRAKSZ2IKnHrf0Q2dyw99)
    - [Technical support](https://share-eu1.hsforms.com/26WB8z3cYTPWv02MIx6nr7w2dyw99)
    - [Finance support](https://share-eu1.hsforms.com/2mMsLOqRLQl2l8S6q3ZbgDA2dyw99)
    - [Report a bug](https://share-eu1.hsforms.com/220XTdV4ZQ726tz1CtoOw7A2dyw99)
    - [Feature request](https://share-eu1.hsforms.com/2g75JWLunRbqueEKBytvYvg2dyw99)
- English
  
  Show submenu for translations

 How can we help you?

- There are no suggestions because the search field is empty.

1. [Maxem Knowledge Base](https://support.maxem.io/?hsLang=en)
2. [Products & Services](https://support.maxem.io/products-services?hsLang=en)
3. [Maxem Energy Controller](https://support.maxem.io/products-services?hsLang=en#maxem-energy-controller)

October 20, 2026

# How do I configure a SMA Data Manager EDMM-20 for communication with the Maxem Energy Controller?

## Follow the steps below to correctly connect the SMA Data Manager to the Maxem Energy Controller and verify that it is online and generating power.

##### **Introduction**

This article explains how to configure a **SMA Data Manager EDMM-20** with the **Maxem Energy Controller**.

##### **Preparation**

A smooth installation requires proper preparation. Before configuring the SMA Data Manager EDMM-20, both the data manager and Maxem’s Energy Controller must be successfully installed to ensure proper communication between the data manager and the controller.

##### **Configuration steps**

###### Step 1: Navigate to SMA's Sunny Portal

1. Open the SMA Data Manager web UI using its IP address.
2. Log in with an **Installer account**.
3. In the top bar, use **Select System** to select the right location from the list.
4. In the top bar, use **Select Device** to select the right data manager from the list.

 

###### Step 2: Configure the static IP address for the data manager

1. In the (left) sidebar, go to **Configuration → Network configuration**.
2. Click on the **Ethernet** section to configure the right settings.
3. Make sure **Disconnect networks** is turned **OFF**.
4. Make sure **Automatic IP assignment via DHCP server** is turned **OFF**.
5. Fill in the designated static IP address **192.168.25.XX** in the **IP address** field.
6. Fill in **255.255.255.0** in the **Subnet mask** field.
7. Fill in **192.168.25.1** in the **Gateway IP** field.
8. Fill in **8.8.8.8** in the **DNS server IP** field.
9. Press **Save** to save these settings.

 

###### Step 3: Enable Modbus TCP on the SMA data manager

1. In the (left) sidebar, go to **Configuration → External communication**.
2. Under **Modbus server**, select **Carry out initial configuration**.
3. Enable **Modbus server**.
4. Verify that the port is set to **502**.
5. The field under **assignment of unit ID** can be left empty.

###### Step 4: Open Grid management service

1. In the top bar, click on the **Home**icon.
2. In the (left) sidebar, go to **Configuration → Grid management service**.
3. Choose **Configuration & activation** for **Active Power**.

 

###### Step 5: Configure Active Power control

In the **Active Power** wizard, verify and set the following options:

1. Check **Total system power** is set correctly for the PV installation.
2. Make sure **Optimized regulation/control mode** is **unchecked**.
3. Select **Open loop control**.
4. Leave all **Signal sources** unchecked.
5. Enable **Direct selling interface**.
6. Select **Standard Modbus interface**.
7. Set **Setting time** to **1**.
8. Set **Active power gradient** to **100**.
9. Press **Save**.

 

###### Step 6: Verify external active power parameters

1. In the (left) sidebar, go to **Configuration → Parameter**.
2. Under **Filter**, enter **External active power**.
3. Verify the following parameter statuses: 
     1. External active power setpoint via Modbus (direct seller) → **ON**
     2. External active power setpoint via Modbus \*electric utility company) **→ OFF**
     3. External active power setpoint **→ ON**
     4. External active power setpoint **→ OFF**

If you change any values, press **Save** at the bottom of the page.

##### **Testing**

After configuration, Maxem can verify whether the energy controller successfully communicates with the SMA Data Manager EDMM-20.

If no successful communication has been established between the SMA Data Mamnager EDMM-20 and the Maxem Energy Controller, and the data mangerer does not appear online in SMA Sunny Portal via the Energy Controller, please repeat the steps from Configuration Steps.

Note: This configuration must be performed by an installer who is experienced in configuring a SMA Data Manager EDMM-20, using the SMA Data Manager EDMM-20 installation manual as a guideline.

---

##### **Manufacturer Manuals**

Download the manufacturers manuals [here](https://www.sma.de/en/service/downloads).

- [Start using Maxem](https://support.maxem.io/start-using-maxem?hsLang=en#main-content)

    - [Contact Maxem Sales](https://support.maxem.io/start-using-maxem?hsLang=en#contact-maxem-sales)
    - [Onboarding](https://support.maxem.io/start-using-maxem?hsLang=en#onboarding)
- [Products & Services](https://support.maxem.io/products-services?hsLang=en#main-content)

    - [Charge Point Management System (CPMS)](https://support.maxem.io/products-services?hsLang=en#charge-point-management-system-cpms)
    - [Energy Management System (EMS)](https://support.maxem.io/products-services?hsLang=en#energy-management-system-ems)
    - [Maxem Energy Controller](https://support.maxem.io/products-services?hsLang=en#maxem-energy-controller)
    - [4G SIM cards](https://support.maxem.io/products-services?hsLang=en#4g-sim-cards)
- [Maxem Energy Cloud](https://support.maxem.io/maxem-energy-cloud?hsLang=en#main-content)

    - [Getting started](https://support.maxem.io/maxem-energy-cloud?hsLang=en#getting-started)
    - [User accounts, Roles and Permissions](https://support.maxem.io/maxem-energy-cloud?hsLang=en#user-accounts-roles-and-permissions)
    - [Charging stations](https://support.maxem.io/maxem-energy-cloud?hsLang=en#charging-stations)
    - [Charge passes](https://support.maxem.io/maxem-energy-cloud?hsLang=en#charge-passes)
    - [Billing](https://support.maxem.io/maxem-energy-cloud?hsLang=en#billing)
    - [Search](https://support.maxem.io/maxem-energy-cloud?hsLang=en#search)
    - [Troubleshooting](https://support.maxem.io/maxem-energy-cloud?hsLang=en#troubleshooting)
    - [Static Load Balancing](https://support.maxem.io/maxem-energy-cloud?hsLang=en#static-load-balancing)
- [Integrated Hardware](https://support.maxem.io/integrated-hardware?hsLang=en#main-content)

    - [Chargers](https://support.maxem.io/integrated-hardware?hsLang=en#chargers)
    - [kWh Meters](https://support.maxem.io/integrated-hardware?hsLang=en#kwh-meters)
    - [Battery Energy Storage System (BESS)](https://support.maxem.io/integrated-hardware?hsLang=en#battery-energy-storage-system-bess)
    - [PV Inverters](https://support.maxem.io/integrated-hardware?hsLang=en#pv-inverters)
- [Subscriptions, invoices and payments](https://support.maxem.io/subscriptions-invoices-and-payments?hsLang=en)
- [Support](https://support.maxem.io/support?hsLang=en#main-content)

    - [Technical support](https://support.maxem.io/support?hsLang=en#technical-support)
    - [Finance support](https://support.maxem.io/support?hsLang=en#finance-support)
    - [Release notes](https://support.maxem.io/support?hsLang=en#release-notes)
    - [Maxem News & Updates](https://support.maxem.io/support?hsLang=en#maxem-news-updates)

[![](https://support.maxem.io/hs-fs/hubfs/Logo-Hi-res-Maxem.png?width=544&height=102&name=Logo-Hi-res-Maxem.png)](http://maxem.energy)

Kabelweg 57, 1014 BA, Amsterdam, NL

[mailto:support@maxem.energy](mailto:support@maxem.energy) <https://www.linkedin.com/company/maxem-energy/>

Copyright © 2025, Maxem